TY - GEN
T1 - Analysis of acceleration in aging insulation due to the effect of humidity and contaminant in induction motor loaded
AU - Muttaqin, Labib Faizul
AU - Asfani, Dimas Anton
AU - Negara, I. Made Yulistya
AU - Dapis,
N1 - Publisher Copyright:
©/2017/IEEE.
PY - 2017/11/28
Y1 - 2017/11/28
N2 - In this study, the experimental of accelerated aging in induction motor insulation is done in a loaded state with high humidity influence and under effects of contaminant. The method used to evaluate the condition of the motor is polarization index (PI), oscillatory response test (surge test) and LCR measurement. PI is used to determine the value of polarization index and custody coil insulation via measured four direct current during the test. Oscillatory response test used to determine differences in the quality of the coil insulation based on the response to the wave oscillation with error area ratio (EAR) method. While the LCR measurement is used to detect the value of inductance, capacitance and resistance arising from the influence of humidity and contaminant in the stator's coil. Furthermore, the output PI variable and oscillation response test and LCR measurement compared to getting the tendency chart damage. Based on test results, EAR method is faster to detect decrease coil insulation in the second test by 30.5 %. Meanwhile, the new PI value was changes in its value in the fourth test. While the LCR value is not significant.
AB - In this study, the experimental of accelerated aging in induction motor insulation is done in a loaded state with high humidity influence and under effects of contaminant. The method used to evaluate the condition of the motor is polarization index (PI), oscillatory response test (surge test) and LCR measurement. PI is used to determine the value of polarization index and custody coil insulation via measured four direct current during the test. Oscillatory response test used to determine differences in the quality of the coil insulation based on the response to the wave oscillation with error area ratio (EAR) method. While the LCR measurement is used to detect the value of inductance, capacitance and resistance arising from the influence of humidity and contaminant in the stator's coil. Furthermore, the output PI variable and oscillation response test and LCR measurement compared to getting the tendency chart damage. Based on test results, EAR method is faster to detect decrease coil insulation in the second test by 30.5 %. Meanwhile, the new PI value was changes in its value in the fourth test. While the LCR value is not significant.
KW - Effect of contaminant
KW - High humidity
KW - Insulation resistance
KW - LCR measurement
KW - Oscillation response test
KW - Polarization index (PI)
UR - http://www.scopus.com/inward/record.url?scp=85043582570&partnerID=8YFLogxK
U2 - 10.1109/ISITIA.2017.8124075
DO - 10.1109/ISITIA.2017.8124075
M3 - Conference contribution
AN - SCOPUS:85043582570
T3 - 2017 International Seminar on Intelligent Technology and Its Application: Strengthening the Link Between University Research and Industry to Support ASEAN Energy Sector, ISITIA 2017 - Proceeding
SP - 169
EP - 174
BT - 2017 International Seminar on Intelligent Technology and Its Application
PB - Institute of Electrical and Electronics Engineers Inc.
T2 - 18th International Seminar on Intelligent Technology and Its Application, ISITIA 2017
Y2 - 28 August 2017 through 29 August 2017
ER -