Abstract
A 20 kV distribution feeder with high-resistance grounding (HRG) at PLN ULP Sutojayan was investigated to address recurrent maloperation of conventional overcurrent and ground-fault protection under low ground-fault current conditions. The feeder neutral is grounded through a 500Ω resistor, which limits single line-to-ground fault current to approximately 25 A and makes fault discrimination more difficult. This study evaluates an analytical and field-validated PT-assisted DGR-VROC coordination framework for a 20 kV high-resistance grounded feeder. The proposed framework combines residual-current and residual-voltage based directional ground fault discrimination, voltage-restrained overcurrent sensitivity adjustment, and coordination-time assessment. Field disturbance records, MATLAB/Simulink time-domain relay modeling, ETAP reliability assessment, and Failure Mode and Effect Analysis (FMEA) are integrated to evaluate both the protection performance and reliability improvement. Field data over two one-year operating periods showed that recloser disturbance events decreased from 70 to 17 after implementation. The reliability indices also improved significantly, with SAIFI decreasing from 3.20 to 0.90 int./ customer.year, SAIDI from 9.60 to 2.30 h/customer.year, and ENS from 2.40 to 0.65 MWh / year. ETAP simulations reproduced the same trend, while FMEA results showed substantial reductions in Risk Priority Number for critical failure modes such as reverse-fault mal-trip and nuisance trip during open-phase conditions. These results demonstrate that the proposed PT-assisted DGR and VROC scheme improves protection selectivity and significantly enhances the reliability of the 20 kV HRG distribution feeder.
| Original language | English |
|---|---|
| Title of host publication | 27th International Seminar on Intelligent Technology and Its Applications, ISITIA 2026 |
| Publisher | Institute of Electrical and Electronics Engineers Inc. |
| Pages | 604-609 |
| Number of pages | 6 |
| ISBN (Electronic) | 9798319521576 |
| DOIs | |
| Publication status | Published - 2026 |
| Event | 27th International Seminar on Intelligent Technology and Its Applications, ISITIA 2026 - Hybrid, Bali, Indonesia Duration: 22 Jul 2026 → 24 Jul 2026 |
Conference
| Conference | 27th International Seminar on Intelligent Technology and Its Applications, ISITIA 2026 |
|---|---|
| Country/Territory | Indonesia |
| City | Hybrid, Bali |
| Period | 22/07/26 → 24/07/26 |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 7 Affordable and Clean Energy
Keywords
- Directional ground relay
- Distribution system reliability
- High-resistance grounding
- Potential Transformer
- Voltage-restrained overcurrent relay