Abstract
This paper introduces the influence on integrating battery energy storage system (BESS) as ancillary controller of wind power plant in small signal stability. Modified two area power system is used as the test system. The modification has been made by replacing one synchronous generator with wind and PV generation. Modal analysis and phase portrait analysis are used to investigate the influence of adding BESS on wind power plant. From the simulation results it is found that the small signal stability performance can be enhance by adding BESS as ancillary controller of wind power plant. This result indicated by increasing damping performance on the critical mode. Furthermore, the oscillatory condition is more damped compared to the base case scenarios. These results indicated by the smallest circular on the phase portrait analysis. Moreover, by adding BESS as ancillary controller the structured singular value (SSV) of the investigated system is 0.8321. It can be stated that the proposed method is robust against uncertainty (SSV must below 1).
Original language | English |
---|---|
Pages (from-to) | 188-198 |
Number of pages | 11 |
Journal | International Journal of Intelligent Engineering and Systems |
Volume | 14 |
Issue number | 5 |
DOIs | |
Publication status | Published - 2021 |
Keywords
- BESS
- Clean energy technology
- Oscillatory stability