Study of the evaporation process in the spray zone of a mechanical draft wet cooling tower

  • Dany Iman Santoso*
  • , Bambang Antoko
  • , Prabowo
  • , Djatmiko Ichsani
  • *Corresponding author for this work

Research output: Contribution to journalArticlepeer-review

3 Citations (Scopus)

Abstract

The evaporation process in the nozzle spray system of a cooling tower was the main object of study in order to determine its performance. This process involves liquid water in small size, usually at the droplet level. At this level, parameters that affect the droplet size, such as capacity, air velocity in the chamber, water pressure at the nozzle, atmospheric temperature, etc., influence the process of heat and mass transfer. In this study, capacity and fan rotation were varied to obtain a graph showing the evaporation. Radius, velocity, mass and temperature graphs and rate graphs were obtained from mathematical modeling of the governing equations. From the results it appears that evaporation occurs at a capacity of 6 liter per minute and above, but this requires further proof of the evaporation process along with the height of the tower, which will be the subject of a future study.

Original languageEnglish
Article number210204
JournalJournal of Engineering and Technological Sciences
Volume53
Issue number2
DOIs
Publication statusPublished - 2021

Keywords

  • Cooling tower
  • Droplet level
  • Evaporation process
  • Heat and mass transfer
  • Nozzle spray

Fingerprint

Dive into the research topics of 'Study of the evaporation process in the spray zone of a mechanical draft wet cooling tower'. Together they form a unique fingerprint.

Cite this