N2 - Harmonic filters are essential components in electric power systems, serving to reduce harmonic distortion that, if uncontrolled, can cause equipment failure, lower system efficiency, and increase power losses. Nonlinear loads, especially those with semiconductor-based devices, are a significant source of harmonics in today's distribution networks. These harmonics degrade power quality and raise the chances of equipment damage and energy inefficiencies. This study investigates the impact of nonlinear loads on harmonic distribution within a radial distribution network, focusing on Substation 2 Tonasa IV at PT. Semen Tonasa. By applying the Whale Optimization Algorithm (WOA) in MATLAB 2021b, the research seeks to optimize harmonic reduction techniques. Simulation results indicate that positioning a harmonic filter at bus 6 is most effective for reducing harmonic spread in the Tonasa IV system. With a single-tuned filter rated at 1109.747 kVAR, the system realizes a total loss reduction of about 4.55%,
AB - Harmonic filters are essential components in electric power systems, serving to reduce harmonic distortion that, if uncontrolled, can cause equipment failure, lower system efficiency, and increase power losses. Nonlinear loads, especially those with semiconductor-based devices, are a significant source of harmonics in today's distribution networks. These harmonics degrade power quality and raise the chances of equipment damage and energy inefficiencies. This study investigates the impact of nonlinear loads on harmonic distribution within a radial distribution network, focusing on Substation 2 Tonasa IV at PT. Semen Tonasa. By applying the Whale Optimization Algorithm (WOA) in MATLAB 2021b, the research seeks to optimize harmonic reduction techniques. Simulation results indicate that positioning a harmonic filter at bus 6 is most effective for reducing harmonic spread in the Tonasa IV system. With a single-tuned filter rated at 1109.747 kVAR, the system realizes a total loss reduction of about 4.55%,
KW - Radial Distribution System (RDS)
KW - Whale Optimization Algorithm (WOA)
KW - harmonics
KW - losses
KW - nonlinear loads
UR - https://www.scopus.com/pages/publications/105019058276
U2 - 10.1109/IDEAS62193.2025.11157292
DO - 10.1109/IDEAS62193.2025.11157292
M3 - Conference contribution
AN - SCOPUS:105019058276
T3 - 2025 IEEE Power Electronics Society International Decentralized Energy Access Symposium, IDEAS 2025
BT - 2025 IEEE Power Electronics Society International Decentralized Energy Access Symposium, IDEAS 2025
PB - Institute of Electrical and Electronics Engineers Inc.
T2 - 2025 IEEE Power Electronics Society International Decentralized Energy Access Symposium, IDEAS 2025
Y2 - 7 January 2025 through 9 January 2025
ER -